Parameter  Range  Function 
Min send intervall    Displays current minimum interval for sending 
values. A value may only be sent a maximum of 
one time during this interval. 
Settings    Go to settings page to parameterize LON bus. 
 
Main Index > System overview > Communication > LON >  LON settings 
 
Parameter  Range  Function 
Send heart beat  0…65535 [s]  Set interval for sending values. 
Receive heart beat  0…65535 [s]  Set interval for receiving values. 
Min send interval  0…65535 [s]  Set minimum interval for sending values. 
 
 
9.3.2  Commission external LON module 
 
Participating devices 
−  Climatix POL 636 controller. 
−  LON module POL906. 
 
Prerequisites for commissioning a LON section: 
–  The SAPRO application is fully commissioned. 
–  Level 4 (password 2000). 
–  Mapping file (OBH.bin) is loaded. 
 
LON bus parameteriza-
tion 
Devices 
Prerequisites 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB