199 / 244
Siemens Standard application AHU CE1P3977en_02
Building Technologies HMI 01.02.2010
Main Index > Unit > Temp control > Tmp setpoints
Parameter Function Value range Unit Standard R S Link
Draught clg max dev Room Flow Limit Cooling Max deviation
Shift the maximum allowed Supply
Temperature according to the Supply-
Room or Exhaust deviation
(only possible with cascade controlling)
0.0…64.0 °C 2.0 6
Fan htg deadzone Deadzone for Fan Heating 0.0…20.0 °C 2.0 6
Fan clg deadzone Deadzone for Fan Cooling 0.0…20.0 °C 2.0 6
Fan comp tmp stpt Temperature Fan compensation Setpoint 0.0…64.0 °C 20.0 6
Fan comp tmp functin Temperature Fan compensation operation
from the Fans
Incease
Decrease
Increase 6
Summer comp Actual Value; Jumpline for Summer
compensation settings
°C 6
Winter comp Actual Value;Jumpline for Winter
compensation settings
°C 6
Sply tmp dev alarm Actual Status; Jumpline for Settings Passive
Active
x
Room tmp dev alarm Actual Status; Jumpline for Settings Passive
Active
x
17.15.3 Temperature setpoints > Summer comp tmp
Main Index > Unit > Temp control > Temperature Setpoints > Summer Comp tmp
Parameter Function Value range Unit Standard R S Link
Outs air tmp start Start Temperature for Summer
compensation
-64…64 °C 25.0 6
Outs air tmp end End Temperature for Summer
compensation
-64…64 °C 30.0 6 Section:
5.5.3
Delta delta for Summer compensation -64…64 K 0.0 6
17.15.4 Temperature setpoints > Winter comp tmp
Main Index > Unit > Temp control > Temperature Setpoints > Winter Comp tmp
Parameter Function Value range Unit Standard R S Link
Outs air tmp start Start Temperature for Winter compensation -64…64 °C 5.0 6 Section:
Outs air tmp end End Temperature for Winter compensation -64…64 °C -20.0 6
5.5.3
Delta delta for Winter compensation -64…64 K 0.0 6
17.15.5 Temperature setpoints > Sply tmp dev alarm
Main Index > Unit > Temp control > Temperature Setpoints > Sply tmp dev alarm
Parameter Function Value range Unit Standard R S Link
Alarm Actual Status Supply Deviation alarm Active…passiv X
Min limit Lowest allowed Present Value for alarm -64…64 °C 10 6 Section:
Maximum deviation In maximum allowed Deviation -64…64 °C 5 6
5.5.4
Start up delay Delay until the Deviation is supervised 0…36000 --- S --- 60 6
17.15.6 Temperature setpoints > Room tmp dev alarm
Main Index > Unit > Temp control > Temperature setpoints > Room tmp dev alarm
Parameter Function Value range Unit Standard R S Link
Alarm Actual Status Supply Deviation alarm Active…passiv X
Min limit Lowest allowed Present Value for alarm -64…64 °C 10 6 Section:
Maximum deviation In maximum allowed Deviation -64…64 °C 10 6
5.5.4
Start up delay Delay until the Deviation is supervised 0…36000 --- S --- 60 6
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 199