No  Room unit parameter/description 
 
006 
 
geographic address room (1.X.1). 
Numbering range for room: 1...14. 
Default value set to 1. 
 
007 
 
geographic address sub zone (RW)(1.1.X). 
Numbering range for sub zone: 1...15. 
This value must be changed from default 1 to 2 for two room units on the 
same controller. 
 
008 
¨ 
Network error recognition on/off (RW). 
Parameter to turn on/off the network error recognition function, with  
0 = off (P__ is displayed when no data frames are received in the last 70 
seconds and the function is turned on). 
1 = On. 
 
NET flashes, when no data frames are received over the past 70 seconds 
and the function is turned on. 
Timeout
 
Network error recognition during parameter initialization: 30 
seconds. 
 
009 
 
Automatic assignment of individual addresses on/off (RW). 
0 = The room unit uses the unit devices as a fixed assigned individual ad-
dress. 
1 = Automatic addressing on the process bus 
The room unit changes as required (e.g. for address conflict on the 
process bus) the individual address via DAA mechanism (Detect And 
Avoid mechanism)  
Default value 1 = automatic addressing 
 
When the controller sends an alarm to the room unit, the  
•  Alarm is displayed 
 
 
•  Depending on parameterization, the alarm number, including the grouping, flash-
es, or only the alarm is displayed 
A = Alarm switched off,  
B = Normal alarm,  
C = Warning 
 
 
Details see 
 19.6 – Alarm lists and  9.5 – Communication room unit 
 
Alarm display 