81 / 244 
Siemens  Standard application AHU  CE1P3977en_02 
Building Technologies  Functions  01.02.2010 
Parameter  Range  Function 
–  Alarm  Go to page with digital input settings. For exam-
ple, you can set the time for jitter protection (De-
fault: 0 s).  
Start updelay fdbk  0...36000 [s]  Defines the period after a pump start without 
feedback before a feedback alarm is triggered. 
Jitter time is enabled exclusively if the feedback 
is pending after this period. 
Off by fdbk alarm  –  No 
–  Yes 
Determines, in the event of a feedback fault, 
whether a pump command is still pending or 
whether to switch off the command. 
Min run time  0...36000 [s]  Define the minimum runtime for the pump after a 
start. In the event of a fault, the evaporator is 
shut down immediately without regard to the 
minimum runtime. 
 
Feedback can only be used as alarm, when Contact function = NO (Normally 
Open) and the element is set to ON. 
 
 
5.10.3  Pump kick 
 
Pump kick is enabled. 
Main Index > Configuration > Configuration 2 > Cooling pump = Yes+Kick 
Main Index > Configuration > Configuration 2 > Cooling 2 pump = Yes+Kick 
The pump is switched on for a short period for longer idle periods. This prevents 
lock up. 
Main Index > Unit > Temp control > Cooling > Pump 
Main Index > Unit > Temp control > Cooling 2 > Pump 
Parameter  Range  Function 
Kick date / time  Mo 00:00...So 23:29  Weekday and time for pump kick. Sets the weekday 
(Mon...Sun) and time to run the pump kick.  
Examples: 
Mon *:*  Each Monday at midnight. 
Sat 07:*  Each Saturday at 7:00 am. 
* *:*  Time is not relevant; the kick interval applies 
accordingly. 
Kick interval  0.0...36000.0 [h]  Idle time for pump kick. Set the idle time after which a 
pump kick is run. Examples: 
168  After 168 hours. 
123.4  After 123 hours and 24 minutes. 
0  Idle time is not relevant; kick date/time applies 
accordingly. 
Kick on time  0.0...36000 [s]  Set the period for the pump kick. 
Examples: 
10  Period = 10 seconds. 
0  Period = 1 controller cycle (ca. 150 ms). 
 
Kick date/time = * *:* and kick interval = 0 --->  
No pump kick is run. 
 
Note 
Prerequisite 
Function 
Parameter 
Note 
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 81