Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
125 
 
P2292 =... 
 
PID output lower limit 
Sets lower limit for the PID controller out
ut in 
%
.
 
PID
MOP
ADC
PID
SUM
PID
PID
FF
USS
BOP link
USS
COM link
CB
COM link
ADC2
P2254
P2253
PID
RFG
PID
PT1
−
∆
PID
P2200
P2264
PID
PT1
PID
SCL
&
P2251
Output
PID
0
1
Motor
control
P2257
P2258
P2261
P2271
P2269
P2270
P2265
P2280
P2285
0
 
 
Example: 
 
Parameter Parameter text  Example 
P2200  BI: Enable PID controller  P2200 = 1.0  PID controller active 
P2253  CI: PID setpoint  P2253 = 2224 PID-FF1 
P2264  CI: PID feedback  P2264 = 755  ADC 
P2267  Max. PID feedback  P2267  Adapt to the application 
P2268  Min. PID feedback  P2268  Adapt to the application 
P2280  PID proportional gain  P2280  Determined by optimizing 
P2285  PID integral time  P2285 Determined by optimizing 
P2291  PID output upper limit  P2291  Adapt to the application 
P2292  PID output lower limit  P2292  Adapt to the application 
 
0.00 %