Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
81 
The following must be noted when entering the rating plate data or the ESB data: 
¾  The outer conductor voltage/phase-to-phase voltage (voltage U
12
 between outer 
conductors L1, L2) and the outer conductor current (phase current) I
1
 are 
always specified on the rating plate. 
¾  The rated motor voltage P0304 and the rated motor current P0305 must always 
be entered according to the motor circuit configuration (either delta/star circuit 
configuration). 
¾  If rated motor data that are available (P0304, P0305) are not consistent with the 
motor circuit configuration, then an appropriate conversion should be made 
which is then entered. 
¾  If equivalent circuit diagram data (P0350, P0354, P0356, P0358, P0360) is 
available, then these should be entered according to the motor circuit 
configuration. If there is no consistency between the motor circuit configuration 
and equivalent circuit diagram data, then the equivalent circuit diagram data 
should be converted and entered corresponding to the data on the rating plate 
(P0304, P0305). 
I
1
1
2
U
12
3
U
1N
I
1N
Z
N
ZZ
III
321
==
U 3
UUU
1Ν
312312
⋅
===
Z2
I
U
1
12
⋅=
3
Z
Z
Y12,
∆12,
=
U
3
U
Y12,
1
∆12,
=
I
1
1
2
U
12
3
I
12
ZZ
Z
I
3
1
III
1312312
⋅===
UUU
312312
==
I
3
1
I
Y1,∆1,
=
Z
3
2
I
U
1
12
⋅=
 
Fig. 3-24  Star / delta circuit configurations 
NOTE 
The precise equivalent circuit diagram data are of extreme important regarding the 
stability of the closed-loop vector control and for the voltage boost applied to the 
V/f characteristic. Equivalent circuit diagram data can only be estimated from the 
rating plate data; this is the reason that equivalent circuit diagram data is either 
determined  
-  using the motor data identification (refer to Chapter 0), or 
-  is entered from a motor data sheet that may be available (refer to Chapter 0). 
 
 
NOTE 
The MICROMASTER series of drive units is not available for 3-ph. 690 V AC.