3  Functions  Issue 10/06 
  MICROMASTER 440      Operating Instructions 
68  6SE6400-5AW00-0BP0 
3.1.4 Reference quantities  
Parameter range:  P2000 – r2004 
Physical quantities are normalized or de-normalized by the frequency inverter 
when data is output or is being entered. This conversion is undertaken by the 
particular interface using the reference quantities. The normalization / de-
normalization is carried-out for the following interfaces: 
Table 3-5  Normalized interfaces 
Interafce 100 % 
Analog input  
Current input 
Voltage input 
 
20 mA 
10 V 
Analog output  
Current output 
Voltage output 
 
20 mA 
10 V 
USS 4000 h 
CB 4000 h 
 
Further, for a BICO connection, a normalization is carried-out if the connector 
output (CO) represents a physical quantity and the connector input (CI) a 
normalized (percentage) quantity (e.g. PID controller). De-normalization is carried-
out if the inverse situation exists. This normalization / de-normalization should be 
carefully taken into consideration, especially for the free function blocks (FFBs).  
Reference quantities (normalization quantities) are intended to allow setpoint and 
actual value signals to be represented in a standard fashion (normalization / de-
normalization of physical quantities such as setpoint and actual frequency). This 
also applies for permanently set parameters that are entered as a "percentage". A 
value of 100 % corresponds to a process data value PZD of 4000 h (USS or CB) – 
or a current / voltage value of 20 mA / 10 V (analog input / output). The following 
reference parameters and permanently saved reference values are available: 
Table 3-6  Normalization functions 
Parameter  Designation  Value (100 % / 4000 h)  Units 
P2000 Reference frequency P2000  Hz 
P2001 Reference voltage  P2001  V 
P2002 Reference current  P2002  A 
P2003 Reference torque  P2003  Nm 
r2004 Reference power 
π 
*
 P2000 
*
 P2003 
kW 
- Reference speed 
P2000 
*
 60 / r0313 
RPM 
-  Reference temperature  100 °C  °C 
-  Reference energy  100 kWh  kWh