Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
97 
3.5.7 Commissioning the application 
After the motor – drive inverter combination was commissioned using the quick or 
series commissioning, in the following step parameters should be adapted and set 
according to the technological requirements. As an example, the following points 
should be considered: 
¾  Functional requirements of the drive inverter (e.g. closed-loop process control 
with PID controller) 
¾ Limit values 
¾ Dynamic requirements 
¾ Starting torques 
¾ Load surge requirement 
¾ Overload 
¾ Diagnostics 
If the application includes a function, which is not covered by the quick or series 
commissioning, then the following sections of the function description or the 
parameter list should be considered. 
Adapting the drive inverter to the application 
The parameters designated with * offer more setting possibilities than are listed 
here. Refer to the parameter list for additional setting possibilities. 
 
 
  Factory setting
P0003 = 3
 
User access level * 
 1  Standard: Allows access into most frequently used parameters 
  2  Extended: Allows extended access e.g. to inverter I/O functions 
  3  Expert (For expert use only) 
3.5.7.1  Serial Interface (USS) 
 
P2010 =... 
 
USS baud rate 
Sets baud rate for USS communication. 
 
P2011 =... 
 
USS address 
Sets unique address for inverter. 
 
P2012 =... 
 
USS PZD length 
Defines the number of 16-bit words in PZD part of USS telegram. 
 
P2013 =... 
 
USS PKW length 
Defines the number of 16-bit words in PKW part of USS telegram. 
Possible  
Settings: 
 4  2400 Baud 
 5  4800 Baud 
 6  9600 Baud 
 7  19200 Baud 
 8  38400 Baud 
 9  57600 Baud 
 10  76800 Baud 
 11  93750 Baud 
 12  115200 Baud 
 
START 
1 
6 
0 
2 
127