Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
173 
Example:  Command source via "USS on BOP link" interface  
  a)  Standard method   
→  P0700 = 4 
  b)  BICO method    →  P1055 = 2032.8 
          P1056 = 2032.9 
         :::: 
          (refer to P0700 for a complete list)  
 
3.11  PID controller (technological controller)  
Parameter range:  P2200 
    P2201 – P2355 
Warnings - 
Faults - 
Function chart number:  FP3300, FP3400, FP5100 
Features: 
-  cycle time:  8 ms 
In addition to the open-loop/closed-loop control of a three-phase motor (standard 
application for a frequency inverter), MICROMASTER has a technology controller. 
This can be used to control process quantities – such as pressure or level. 
Depending on the application, different control structures are required to control 
process quantities. For MICROMASTER, the following structures have been 
integrated; these can be selected or de-selected using parameters P2200, P2251 
(also refer to Fig. 3-53): 
a)  Variable-speed drive (VSD) 
b)  Closed-loop PID control 
c)  Closed-loop dancer roll control 
 
The PID controller – integrated in MICROMASTER – is required for control 
structures b) and c). The frequency inverter can address many new applications 
using the higher-level control (closed-loop PID/dancer roll control). The following 
typical applications can be implemented: 
¾  Closed-loop pressure control for extruders 
¾  Closed-loop water level control for pump drives 
¾  Closed-loop temperature control for fan drives 
¾  Closed-loop dancer roll position control for winder applications 
¾  And similar control tasks