Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
219 
NOTE 
¾  When the minimum DC link voltage V
DC_min
 is fallen below, fault F0003 
"Undervoltage" is output and the drive inverter is shut down. The shutdown 
threshold V
DC_min
 depends on the drive inverter type / line supply voltage.  
Table 3-34  DC link undervoltage – shutdown threshold 
Drive inverter type / line supply voltage  Shutdown threshold V
DC_min
 
1-ph. 200 V – 240 V AC ± 10 % 
215 V 
3-ph. 200 V – 240 V AC± 10 % 
215 V 
3-ph. 380 V – 480 V AC ± 10 % 
430 V 
3-ph. 500 V – 600 V AC ± 10 % 
530 V 
 
 
3.19  Positioning down ramp 
Parameter range:  P0500 
    P2480 – r2489 
Warnings - 
Faults - 
Function chart number:  - 
The positioning down ramp (enabled using P0500) can be used for applications 
where it is necessary that a residual distance is moved-through up to the stop 
dependent on an external event (e.g. BERO switch). In this case, MICROMASTER 
440 generates a continuous braking ramp by selecting OFF1 depending on the 
actual load speed / velocity. The drive is then stopped/positioned along this braking 
ramp (refer to Fig. 3-85). 
Motor Gear
f
⋅==
2
1
  P2488  s
t
OFF1
f
 OFF1
 
.
 t 
P2488
.
t
P2488
f
OFF1
 
Fig. 3-85  Positioning down ramp 
In this case, the remaining distance P2488 moved through must be entered, 
referred to the load. In order to carry-out the residual distance calculation on the 
load side, the mechanical arrangement of the axis (gearbox ratio, linear or rotary 
axis) must be appropriately parameterized (refer to Fig. 3-86).