Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
167 
3.8  Fixed frequencies (FF)  
Number: 15 
Parameter range:  P1001 – P1028 
Warnings - 
Faults -  
Function chart number:  FP3200, FP3210 
A setpoint can be entered via the analog inputs, the serial communication 
interfaces, the JOG function, the motorized potentiometer as well as also using 
fixed frequencies. The fixed frequencies are defined using parameters P1001 – 
P1015 and selected via binector inputs P1020 – P1023, P1025, P1026. The 
effective fixed frequency setpoint is available via connector output r1024 which 
means that it can be connected further. If this is to be used as setpoint source, then 
either parameter P1000 or P0719 should be modified or BICO parameter r1024 
should be connected to the main setpoint P1070 or supplementary setpoint P1075. 
Contrary to parameter P0719, when parameter P1000 is modified, this implicitly 
changes BICO parameters P1070, P1075.  
Example:  Fixed frequencies as setpoint source 
a)  Standard method  
→   P1000 = 3 
b)  BICO method     
→   P1070 = 1024,  P1075 = 0 
 
3 methods are available when selecting the fixed frequencies. 
Direct selection 
In this particular mode, the control signal directly selects the fixed frequency. This 
control signal is entered via the binector inputs. If several fixed frequencies are 
simultaneously active, then the selected frequencies are added
. 
Table 3-22  Example for direct coding via digital inputs 
FF1 P1001 0 0 0 0 0 1
FF2 P1002 0 0 0 0 1 0
FF3 P1003 0 0 0 1 0 0
FF4 P1004 0 0 1 0 0 0
FF5 P1005 0 1 0 0 0 0
FF6 P1006 1 0 0 0 0 0
FF1+FF2 0 0 0 0 1 1
…
…
FF1+FF2+FF3+FF4+FF5+FF6 1 1 1 1 1 1
DIN6 DIN5 DIN4 DIN3 DIN2 DIN1
FF0 0 Hz 0 0 0 0 0 0
 
 
The fixed frequencies can be selected via the digital inputs as well as also via 
serial communication interfaces. The fixed frequency is selected, when using digital 
inputs, using 2 techniques. This will be shown in the following example using the 
fixed frequency P1001 and digital input 1 (refer to Fig. 3-49). 
a)  Standard methods 
→  P0701 = 15 
b)  BICO methods   
→  P0701 = 99,  P1020 = 722.0, P1016 = 1