3  Functions  Issue 10/06 
  MICROMASTER 440      Operating Instructions 
178  6SE6400-5AW00-0BP0 
3.11.1.2 PID fixed setpoint (PID-FF) 
Number: 15  
Parameter range:  P2201 – P2228 
Warnings - 
Faults - 
Function chart number:  FP3300, FP3310 
Analog to the fixed frequencies (refer to Section 3.7), the PID controller has 
separate programmable PID fixed setpoints. The values are defined using 
parameters P2201 – P2215 and are selected using binector inputs P2220 – P2223, 
P2225, P2226. The selected PID fixed setpoint is available via connector output 
r2224 where it can be further processed (e.g. as PID main setpoint 
→ P2253 = 
2224).  
3 methods are available to select the PID fixed setpoints, analog to the fixed 
frequencies (Section 3.7):  
¾ Direct selection 
¾  Direct selection + ON command 
¾  Binary-coded selection + ON command 
The methods are selected using parameters P2216 – P2219, P2225, P2227. 
P
2
2
1
6
P0701 = 15
or
P0701 = 99, P2220 = 722.0, P2216 = 1
DIN1
r2224
r0722.0
P2220
1
2,3
P2201
0
. . . .
0
. . . .
. . . .
 
Fig. 3-56  Example to directly select the PID fixed frequency of fixed frequency 1 via 
DIN1