3.5.7.20 Diagnostic parameters 
 
r0035 
 
CO: Motor temperature 
Displays the measured motor temperature in °C. 
 
r0036 
 
CO: Frequency inverter utilization 
Displays the frequency inverter utilization as a % referred to the overload. In so doing, the 
value is calculated using the I
2
t model. 
The I
2
t actual value relative to the maximum possible I
2
t value provides the level of 
utilization.
 
 
r0052 
 
CO/BO: Act. status word 1 
Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be 
used to diagnose the inverter status.
 
 
r0054 
 
CO/BO: Control word 1 
Displays the first control word (STW) of the frequency inverter and can be used to display 
the active commands.
 
 
r0063 
 
CO: Actual frequency 
Displays the actual frequency in Hz. 
V/f
0
1,2
SLVC
(observer
model)
Encoder
P0400
P1300
160 ms
Frequency actual values:
Smoothed freq. actual value
Frequency actual value
Freq.act.value fr. the encoder
21,23
20,22
<20
0
P1300 = 21,23 and P0400 = 0 --> F0090
 P0408  60 
r0313
⋅
Smoothed speed act. value
 r0313 
60
r0022
r0021
r0063
r0061
 
r1079 
 
CO: Selected frequency setpoint 
Displays the selected frequency setpoint. 
The following frequency setpoints are displayed: 
r1078  total setpoint (HSW + ZUSW) 
P1058  JOG frequency, clockwise 
P1059  JOG frequency, counter-clockwise. 
 
r1114 
 
CO: Freq. setpoint after dir. ctrl. 
Displays the setpoint (reference) frequency in Hz after the function block to reverse the 
direction of rotation. 
 
r1170 
 
CO: : Frequency setpoint after RFG 
Displays the total frequency setpoint (reference value) in Hz after the ramp-function 
generator.