3  Functions  Issue 10/06 
  MICROMASTER 440      Operating Instructions 
140  6SE6400-5AW00-0BP0 
3.6.3  Analog inputs (ADC)  
Number: 2 
Parameter range:  P0750 – P0762 
Function chart number:  FP2200 
Features: 
-  cycle time:  4 ms 
-  resolution:  10 bits     
-  accuracy:  1 % referred to 10 V / 20 mA     
-  electrical features:  incorrect polarity protection, short-circuit proof   
Analog setpoints, actual values and control signals are read-into the drive inverter 
using the appropriate analog inputs and are converted into digital signals / values 
using the ADC converter. 
The setting as to whether the analog input is a voltage input (10 V) or a current 
input (20 mA) must be selected using the 2 switches DIP1(1,2) on the I/O board as 
well as also using parameter P0756 (refer to Fig. 3-31). 
 
Possible settings of P0756:  
0   Unipolar voltage input ( 0 to +10 V ) 
1   Unipolar voltage input with monitoring (0 to 10 V ) 
2   Unipolar current input (0 to 20 mA) 
3   Unipolar current input with monitoring (0 to 20 mA) 
4   Bipolar voltage input (-10 V to +10 V) only ADC1
 
Fig. 3-31  DIP switch and P0756 for ADC current / voltage input 
NOTE 
¾  The setting (analog input type) of P0756 must match that of switch DIP1(1,2) on 
the I/O board. 
¾  The bipolar voltage input is only possible with analog input 1 (ADC1). 
Depending on the ADC type or source, the appropriate connection must be made. 
Using, as an example, the internal 10 V voltage source, a connection is shown as 
an example in the following diagram (refer to Fig. 3-32).