Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
83 
3.5.3 Quick commissioning 
If there is still no appropriate parameter set for the drive, then a quick 
commissioning must be carried-out for the closed-loop Vector control and for the 
V/f control including a motor data identification routine. The following operator units 
can be used to carry-out quick commissioning: 
¾ BOP (option) 
¾ AOP (option) 
¾  PC Tools (with commissioning program STARTER, DriveMonitor) 
When the quick commissioning is carried-out, the motor – drive inverter is basically 
commissioned; the following data must be obtained before quick commissioning is 
started:  
¾  Line supply frequency 
¾  Motor rating plate data  
¾  Command / setpoint sources 
¾  Min. / max. frequency or ramp-up / ramp-down time 
¾  Closed-loop control mode 
¾  Motor data identification 
Parameterizing the drive with BOP or AOP 
The frequency inverter is adapted to the motor using the quick commissioning 
function and important technological parameters are set. The quick commissioning 
shouldn't be carried-out if the rated motor data saved in the frequency inverter 
(4-pole 1LA Siemens motor, star circuit configuration 
 frequency inverter (FU)-
specific) match the rating plate data. 
Parameters, designated with a * offer more setting possibilities than are actually 
listed here. Refer to the parameter list for additional setting possibilities. 
NOTE 
¾  Parameter P0308 or P0309 can only be viewed on the BOP or AOP if P0003 ≥ 
2. Depending on the setting of parameter P0100, either P0308 or P0309 is 
displayed. 
¾  The value entered into P0307 and all of the other power data – depending on 
P0100 – are either interpreted as kW or hp value. 
 
 
 
  Factory setting
 
P0003 = 3 
 
 
User access level * 
 1  Standard: Allows access into most frequently used parameters 
  2  Extended: Allows extended access e.g. to inverter I/O functions 
  3  Expert (For expert use only) 
 
Parameter filter * 
 0  All parameters 
 2  Inverter 
 3  Motor 
 4  Speed sensor
 
START 
P0004 = 0 
0 
1