MICROMASTER 440 Operating Instructions
84 6SE6400-5AW00-0BP0
P0010 = 1
Commissioning parameter *
0 Ready
1 Quick commissioning
30 Factory setting (refer to Section 3.5.9)
NOTE
P0010 should be set to 1 in order to parameterize the data of the motor rating
plate.
P0100 =...
P0100 = 1, 2
P0100 = 0
Europe/ North America
(enters the line supply frequency)
0 Europe [kW],
frequency default 50 Hz
1 North America [hp], frequency default
60 Hz
2 North America [kW], frequency default
60 Hz
NOTE
For P0100 = 0 or 1, the setting of switch DIP50/60 determines the value of
P0100 (refer to Section 3.5.1).
OFF = kW, 50 Hz
ON = hp, 60 Hz
Inverter application (enters the required torque)
0 Constant torque (e.g. compressors, processing machines)
1 Variable torque (e.g. pumps, fans)
NOTE
This parameter is only effective for drive inverters 5.5 kW / 400 V
Select motor type
1 Asynchronous motor (induction motor)
2 Synchronous motor
NOTE
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are
permitted.
P0304 =...
P0304 =...
Rated motor voltage
(Nominal motor voltage [V]
from rating plate)
The rated motor voltage on the rating
plate must be checked, regarding the
star/delta circuit configuration to
ensure that it matches with the circuit
connection configured at the motor
terminal board
P0305 =...
P0305 =...
Rated motor current
(Nominal motor current [A]
from rating plate)
P0307 =...
P0307 =...
Rated motor power
(Nominal motor power [kW/hp]
from rating plate)
If P0100 = 0 or 2, value will be in kW.
If P0100 = 1, value will be in in hp.
P0304
P0305
P0307
P0308 P0311
P0310
Example of a typical motor rating plate (data for
a delta circuit configuration).
The precise definition and explanation of this
data is specified in DIN EN 60 034-1.
P0308 =...P0308 =...
Rated motor cosPhi
(Nominal motor power factor (cos ϕ) from rating plate)
If the setting is 0, the value is automatically calculated
P0100 = 1,2: P0308 no significance, no entry required.
P0309 =...
P0309 =...
Rated motor efficiency
(Nominal motor efficiency in [%] from rating plate)
Setting 0 causes internal calculation of value.
P0100 = 0: P0309 no significance, no entry required.
1
0
P0300 =...
P0300 =...
P0205 =...
P0205 =...
0
0
FU-spec.
FU-spec.
FU-spec.
FU-spec.
FU-spec.