3  Functions  Issue 10/06 
  MICROMASTER 440      Operating Instructions 
84  6SE6400-5AW00-0BP0 
 
P0010 = 1 
 
 
Commissioning parameter * 
 0  Ready 
  1  Quick commissioning  
30  Factory setting (refer to Section 3.5.9) 
NOTE 
P0010 should be set to 1 in order to parameterize the data of the motor rating 
plate.
 
P0100 =...
 
 
  P0100 = 1, 2
 
     P0100 = 0 
Europe/ North America  
(enters the line supply frequency) 
 0  Europe [kW],
 frequency default 50 Hz 
  1  North America [hp], frequency default
 60 Hz  
  2  North America [kW], frequency default
 60 Hz 
NOTE 
For P0100 = 0 or 1, the setting of switch DIP50/60 determines the value of 
P0100 (refer to Section 3.5.1). 
    OFF =  kW, 50 Hz  
    ON  =  hp, 60 Hz
 
 
Inverter application (enters the required torque) 
  0  Constant torque (e.g. compressors, processing machines) 
  1  Variable torque (e.g. pumps, fans) 
NOTE 
This parameter is only effective for drive inverters ≥ 5.5 kW / 400 V
 
 
Select motor type 
  1  Asynchronous motor (induction motor) 
 2  Synchronous motor 
NOTE 
For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are 
permitted. 
 
P0304 =... 
P0304 =...
Rated motor voltage 
(Nominal motor voltage [V] 
from rating plate) 
The rated motor voltage on the rating 
plate must be checked, regarding the 
star/delta circuit configuration to 
ensure that it matches with the circuit 
connection configured at the motor 
terminal board
 
 
P0305 =... 
P0305 =...
Rated motor current 
(Nominal motor current [A] 
from rating plate) 
 
P0307 =... 
P0307 =...
Rated motor power 
(Nominal motor power [kW/hp] 
from rating plate) 
If P0100 = 0 or 2, value will be in kW. 
If P0100 = 1, value will be in in hp. 
P0304
P0305
P0307
P0308 P0311
P0310
 
Example of a typical motor rating plate (data for 
a delta circuit configuration). 
The precise definition and explanation of this 
data is specified in DIN EN 60 034-1. 
 
 
P0308 =...P0308 =... 
Rated motor cosPhi 
(Nominal motor power factor (cos ϕ) from rating plate) 
If the setting is 0, the value is automatically calculated  
P0100 = 1,2: P0308 no significance, no entry required.
 
 
P0309 =... 
 
P0309 =...
Rated motor efficiency 
(Nominal motor efficiency in [%] from rating plate) 
Setting 0 causes internal calculation of value. 
P0100 = 0: P0309 no significance, no entry required.
 
1 
0 
 
P0300 =... 
P0300 =...
 
P0205 =... 
P0205 =...
0 
0 
FU-spec.
FU-spec.
FU-spec.
FU-spec.
FU-spec.