Issue 10/06   3  Functions 
MICROMASTER 440      Operating Instructions   
6SE6400-5AW00-0BP0 
143 
With parameter P0775 = 1, negative values can be avoided on the input side of the 
DAC channel. If this parameter is activated, the absolute value is always entered in 
the input of the DAC scaling (the DAC characteristic is mirrored on the Y axis).  
If the value was originally a negative one, the corresponding bit in r0785 is set for 
detection. 
NOTE 
The analog outputs only provide current outputs (0 ... 20 mA). A 0 ... 10 V voltage 
signal can be generated by connecting a 500 Ohm resistor across the outputs. The 
voltage drop across the resistor can be read using parameter r0774 if the 
parameter P0776 is changed-over from current output (P0776 = 0) to voltage 
output (P0776 = 1). The D/A scaling parameters P0778, P0780 and the D/A 
converter dead zone must still be entered in mA (0 ... 20).