Issue 10/06 3 Functions
MICROMASTER 440 Operating Instructions
6SE6400-5AW00-0BP0
159
Correspondingly, the
Response IDs are transferred in the telegram from the slave
to the master at this position. Depending on the request ID, only specific response
IDs are possible.
Table 3-20 Response ID (converter -> master)
Response
ID
Significance
Request
ID
0 No response 0
1 Transfer parameter value (word) 1, 2 or 14
2 Transfer parameter value (double word) 1, 3 or 13
3 Transfer descriptive element
1
4 or 5
4 Transfer parameter value (array, word)
2
6, 7 or 12
5 Transfer parameter value (array, double word)
2
6, 8 or 11
6 Transfer the number of array elements 9
7 Request cannot be executed (with fault number) 1 or 15
8 The PKW interface does not have master authority
2, 3, 5, 7, 8,
11-14 or 15
9
Parameter change report (word)
MICROMASTER does not support this
-
10
Parameter change report (double word)
MICROMASTER does not support this
-
11
Parameter change report (array, word)
2
MICROMASTER does not support this
-
12
Parameter change report (array, double word)
2
MICROMASTER does not support this
-
13 Reserved -
14 Reserved -
15
Transfer text
MICROMASTER does not support this
15
1
The required element of the parameter description is specified in IND (2nd word)
2
The required element of the indexed parameter is specified in IND (2nd word)