3  Functions  Issue 10/06 
  MICROMASTER 440      Operating Instructions 
176  6SE6400-5AW00-0BP0 
Example:  Permanent PID controller should fulfill the following 
secondary conditions: 
PID controller enable and PID setpoint input via PID fixed 
frequencies and PID actual value via the analog input
 
 Parameterization: 
a)  Permanent PID controller enable:   P2200 = 1.0  
b)  Setpoint input via PID-FF:      P2253 = 2224 
c)  Actual value input via analog input ADC:  P2264 = 755 
d)  Setpoint input via PID:      P2251 = 0 
The supplementary (additional) setpoint is added to the main setpoint (PID-SUM) 
and the sum is fed to the setpoint filter (PID-PT1) at the setpoint-actual value 
summation point via the PID ramp-function generator (PID-RFG). The source of the 
supplementary setpoint (BICO parameter P2254), the ramp-up / ramp-down times 
of the PID ramp-function generator (P2257, P2258) as well as also the filter time 
(P2261) can be adapted to the particular application by appropriately 
parameterizing the corresponding parameters. 
Similar to the PID setpoint branch, the actual value branch of the technological 
controller has a filter (PID-PT1) which can be set using parameter P2265. In 
addition to the smoothing, the actual value can be modified using a scaling unit 
(PID-SCL). 
The technological controller can be parameterized as either P, I, PI or PID 
controller using parameters P2280, P2285 or P2274. 
+
-
d
dt
+
+
0
1
PID
setpoint
P2274
P2263
PID
feedback
r2262
r2272
Kp Tn
P2285P2280
r2273
Motor
control
x
y
P2291
P2293
P2293
P2292
r2294
Fig. 3-55  PID controller 
For specific applications, the PID output quantity can be limited to defined values. 
This can be achieved using the fixed limits - P2291 and P2292. In order to prevent 
the PID controller output exercising large steps at power-on, these PID output limits 
are ramped-up with ramp time P2293 from 0 to the corresponding value P2291 
(upper limit for the PID output) and P2292 (lower limit for the PID output). As soon 
as these limits have been reached, the dynamic response of the PID controller is 
no longer limited by this ramp-up/ramp-down time (P2293).