3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions
190 6SE6400-5AW00-0BP0
Table 3-29 Examples for settings of parameter P0810
Parameter setting Command source
P0810 = 722.2 requires P0703 = 99 Digital input 3
P0810 = 2032.15 USS at the BOP link
P0810 = 2036.15 USS at the COM link
P0810 = 2090.15 CB at the COM link
Table 3-30 Possible settings for parameters P0700 and P1000
Valu
e
Command source (P0700) Valu
e
Setpoint source (P1000)
1 BOP (keyboard) 1 MOP setpoint
2 Terminal strip 2 Analog setpoint
4 USS at the BOP link 3 Fixed frequency
5 USS at the COM link 4 USS at the BOP link
6 CB at the COM link 5 USS at the COM link
6 CB at the COM link
7 Analog setpoint 2
10 No main setpoint + MOP setpoint
...
77 Analog setpoint 2 + analog setpoint 2