EasyManua.ls Logo

Siemens MICROMASTER 440 - Page 228

Siemens MICROMASTER 440
312 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Functions Issue 10/06
MICROMASTER 440 Operating Instructions
228 6SE6400-5AW00-0BP0
r0631
ADC
5 V
Signal
loss
detection
T
1
= 4 s
2
1
No sensor
PTC
KTY
0
P0604
Fault
F0015
&
P0601 = 2
Thermal
motor
model
r0633
r0632
r0035
1≥
Motor
i2t
temp.
reaction
P0610
P0601
Equivalent
circuit data
P
V,mot
Power dissipation
V
?
0
1
0
1
r0052
Bit13
PTC
KTY
Fig. 3-93 Thermal motor protection
Temperature rise classes
In drive technology, temperature rise issues play a decisive role when
dimensioning electrical machinery. Different temperature limits apply for the various
materials used in electric motors. Depending on the insulating material being used,
a differentiation is made according to thermal classes (refer to the motor rating
plate) with defined limit temperatures. An excerpt from IEC85 is provided in Table
3-36.
Max.perm.temperatureThermal Class
Y
A
E
B
F
90 °C
105 °C
120 °C
130 °C
155 °C
H180 °C
Excerpt from IEC 85
Table 3-36 Thermal classes
For the temperature model or the KTY84 sensor, the appropriate value ϑ
warn
must
be calculated and entered into parameter P0604 (temperature warning threshold,
default: 130°C). The following applies:
1.1
trip
warn
P0604
ϑ
=ϑ=

Table of Contents