6  Options  Issue 10/06 
  MICROMASTER 440      Operating Instructions 
274  6SE6400-5AW00-0BP0 
6.2  Inverter-dependent options  
Frame Sizes A to F 
¾  EMC filter. Class A 
¾  EMC filter. Class B 
¾  Additional EMC filter. Class B  
¾  Low leakage Class B filter 
¾  Line commutating choke 
¾ Output choke 
¾ Gland plate 
¾ LC filter 
CAUTION 
When using output reactors and LC filters, operation up to a pulse frequency of 
4 kHz only is permitted. Please ensure that the automatic pulse frequency 
reductions are also deactivated. Mandatory parameter settings when using an 
output reactor: P1800 = 4 kHz , P0290 = 0 or 1. 
Frame Sizes FX and GX 
¾  Line commutating choke 
¾  EMC filter. Class A (power commutating choke required) 
¾ LC filter 
CAUTION 
When using output reactors and LC filters, operation up to a pulse frequency of 
4 kHz only is permitted. Please ensure that the automatic pulse frequency 
reductions are also deactivated. Mandatory parameter settings when using an 
output reactor: P1800 = 4 kHz , P0290 = 0 or 1.