Issue 10/06 2 Installation
MICROMASTER 440 Operating Instructions
6SE6400-5AW00-0BP0
45
Frame Sizes D and E
The Gland Plate is factory fitted. If the installation conditions are restricted, the
shield of the motor cable can also be attached outside the cabinet, as shown in
Fig. 2-14, for example.Frame Sizes FX and GX
Frame size F
The gland plate for the control cables is factory-fitted.
Devices without filter: The shield of the motor cable must be attached outside the
cabinet, as shown in Fig. 2-14, for example.
Devices with filter: The gland plate for the motor cable is factory-fitted.
Frame Sizes FX and GX
Connect the wire shields to the shield connection points shown in the connection
drawing (see Fig. 2-9 and Fig. 2-10) .
Twist the shields of the motor cables and screw them to the PE connection for the
motor cable.
When using an EMI filter, a power commutating choke is required. The wire shields
should be fastened to the metallic mounting surface as close as possible to the
components.