9 Operation at Use of a PC
9.3 Configuration of the Device
200 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
The Measured Value Recorder Intervals and the PQDIF Files
The measured values recorder intervals are defined according to the averaging intervals setting. This will define
the availability of the PQDif files.
Table 9-17 PQDIF File Interval (measured value recorder)
Set
averaging
interval
Recording
duration for
creating a PQDIF
file
Time at start of
recording of a
complete
PQDIF file
Start of recording (recorder start option)
30 s 1 h 00:00 h
01:00 h
02.00 h
....
22:00 h
23:00 h
- start at the next minute limit
- start at the next 10-minute limit
- immediate start
- start at the next hour limit
- start next day
1 min 2 h 00:00 h
02:00 h
04.00 h
....
20:00 h
22:00 h
10 min 2 h, 4 h, 6 h, 12 h,
24 h
15 min
30 min
1 h
2 h
MAN_SICAM_Q100_US.book Page 200 Wednesday, June 5, 2019 9:31 AM