9 Operation at Use of a PC
9.3 Configuration of the Device
203SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.6.4 Mains Signaling Voltage
Default Settings and Setting Ranges
Changing the Mains Signaling Voltage Parameters
To change the Mains signaling voltage, proceed as follows:
In the navigation window, select the Recording and Reporting menu and click Mains signaling voltage.
Table 9-18 Mains Signaling Voltage
Parameter Default Setting Setting Range
Mains signaling voltage measurement
MSV active no no
yes
No. of MSV frequencies 1 frequency 1 frequency
2 frequencies
Frequency 1 216.60 Hz 100 Hz to 3 kHz
Frequency 2 1060.00 Hz 100 Hz to 3 kHz
Mains signaling voltage capture setting
Detection threshold 1 [% of Udin] 1 % to 15 % of Udin
Total recording duration 75 s 15 s to 120 s in 15-s steps
Pretrigger ratio 10 % 0 % to 30 % in 5-% steps