9 Operation at Use of a PC
9.3 Configuration of the Device
227SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
date and time when the certificates are uploaded. If no certificate exists in the device, no connection to the
broker can be established.
Figure 9-65 Information above Upload Certificates
NOTE
The Q100 device cannot connect to the OPC UA PubSub (MQTT) broker in any of the following cases:
• The date and time of the device are not synchronized.
• The security certificates and time stamps have expired.
Therefore, you must check the date and time of the device to ensure that they are synchronized, for example,
by selecting Information -> Show device information.