9 Operation at Use of a PC
9.3 Configuration of the Device
242 SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
9.3.7.5.2 Mapping – Measured Values 1-15
At Measured values 1-8 and Measured values 9-15, the measured values are defined which are read by a
selected Modbus slave device.
Default Settings and Setting Ranges of the Modbus Slave Device 1
1)
If the name is also to be displayed on the device display without text overlappings, Siemens recommends
using max. 10 characters.
Table 9-33 Settings for assignment of the measured values of the Modbus slave device 1
Parameter Default Setting Setting Range
Name MV x Slv 1
(x = 1 to 15)
Max. 31 characters
1)
Unit
Note on frequency measured
values:
If a frequency measured value
(unit: Hz) has been parameterized
without a multiplier (multiplier: -), an
additional check is made whether
the resulting value is in the range of
15 Hz to 65 Hz. Measured values
outside this range are marked as in-
valid.
Multiplier: -
Unit: -none-
Acc. to list box
(see chapter 16)
Selecting a multiplier for the following
units is not recommended and will be re-
jected:
-none-
°
°C
°F
%
Register type -none- -none-
Input registers
Holding registers
For -none-, the assignment is ignored
and the corresponding measured value
cannot be selected for other functions.
Data format on bus
(see also Table 9-34.)
Float32 (2 registers) Float32 (2 registers)
Int16 (1 register)
Int16_Ung8000h (1 register)
UInt16 (1 register)
UInt32 (2 registers)
Register number 1 1 to 65 535
Scaling factor 1.000 Any float value
0.00: resulting measured value = 0.00
MAN_SICAM_Q100_US.book Page 242 Wednesday, June 5, 2019 9:31 AM