9 Operation at Use of a PC
9.3 Configuration of the Device
243SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
Table 9-34 Data Format on Bus
Data Format
on Bus
Description Setting Range Invalid
recognition
Used by (example)
Float32
(2 registers)
IEEE Float value -10
38
to +10
38
NaN = invalid
INF = overflow
SENTRON PAC3x00,
SICAM AI 7XV5674,
SICAM T 7KG966,
SICAM P50 7KG775
Int16
(1 register)
16-bit signed
integer
- 32 768 to +32 768 none SENTRON 3WL/3VL
SICAM P50 7KG775
Int16_Ung8000h
(1 register)
16-bit signed
integer
-32768 bis +32768 -32768 (8000h)
= invalid
SIPROTEC 4
UInt16
(1 register)
16-bit integer,
0
0 to +65 535 none SENTRON 3WL/3VL
UInt32
(2 registers)
32-bit integer,
0
0 to +4 294 967 295 none SIPROTEC 4,
SENTRON 3WL/3VL