10 Operation at Use of the Display
10.4 Parameterization
355SICAM Q100, 7KG95xx, Device Manual
E50417-H1040-C522-A6, Edition 06.2019
1) After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later re-open these connections.
Current - Deadband 5 % 1 % to 5 % in increments of 1 %
Power - Deadband 5 % 1 % to 5 % in increments of 1 %
Power factor - Deadband 5 % 2% to 5 % in increments of 1 %
Frequency - Deadband 0,05 0.02 %
0.05 %
Table 10-8 Serial Communication Settings – Modbus RTU and Modbus RTU Master Bus Protocols
Parameter Default Setting Setting Range
Bus protocol Modbus RTU None
Modbus RTU
Modbus Master
Bus Protocol Modbus RTU (Slave)
Device address 1 1 to 247
Baud rate 19 200 bit/s For the selection, see chapter 16
Parity Even For the selection, see chapter 16
Access rights Full Full
Read only
Communication supervision time 600 * 100 ms 0 s = none
100 ms to 6 553 400 ms
Bus Protocol Modbus RTU Master
Baud rate 19 200 bit/s For the selection, see chapter 16
Parity even For the selection, see chapter 16
Additional inter-character timeout 1 ms 0 ms to 100 ms
Maximum 0x/1x register gap 40 0 to 200
Maximum 3x/4x register gap 10
Table 10-7 Ethernet Communication Settings (cont.)
MAN_SICAM_Q100_US.book Page 355 Wednesday, June 5, 2019 9:31 AM