Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-115
Edition 12.2003
Rules:
• The communications reference must correspond with that configured
in CFC (address stage 1 at the address connection).
• The local LSAP must correspond to the "Remote LSAP" data at the
remote receivers.
• The broadcast LSAP 63 or another LSAP is the remote LSAP
(multicast LSAP)
• The maximum PDU length should only be changed if a receiver
cannot handle the specified length.
Features:
• Freely-configurable communications association
• SIMADYN D can be both server as well as also client
Application:
• Communications association, where both communication partners are
client and server.
Communications reference : Type: Unspecified
Association type : Local LSAP :
Remote address : Remote LSAP :
Max. PDU length : 241 Monitoring interval : 0 s
Multiplier :
Password : 0 Group : 0
Profile : 0 0
Supported utilities :
Read : No Write : No
Get OV (detailed version) : No Information report : No
Symbolic addressing : No
Max. number of parallel tasks:
Transmitting : 1 Receiving : 1
Name :
Table 3-53 Mask, "Unspecified"
Non-specified

Table of Contents

Other manuals for Siemens SIMADYN D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMADYN D and is the answer not in the manual?

Siemens SIMADYN D Specifications

General IconGeneral
BrandSiemens
ModelSIMADYN D
CategoryControl Systems
LanguageEnglish

Related product manuals