Communications configuring
3-126 System- and communication configuring D7-SYS - SIMADYN D
Edition 12.2003
Communications reference : 3 Type: Non-cyclic server
Association type : MMAZ Local LSAP : 12
Remote address : 1 Remote LSAP : 11
Max. PDU length : 241 Monitoring interval : 30 s
Supported utilities :
Read : .ind Write : .ind
Get OV (detailed version) : .ind Information report : No
Symb. addressing : .ind
Max. number of parallel tasks:
Transmitting : 0 Receiving : 2
Name : SERV 1
Table 3-57 Mask, "Non-cyclic server": Station 3, communications association 3
Explanation:
• The entries are selected, so that they correspond with those of station
1, communications relationship 6.
Comment:
• For station 1, communication associations 3, 4 and 5 (possibly, only
as dummy) must be defined as well as for station 3, communications
association 2.
Station 3,
communications
association 3