Communications configuring
System- and communication configuring D7-SYS - SIMADYN D 3-161
Edition 12.2003
• Telegram runtime: s 366.
µ
• All of the telegrams are sent immediately one after the other.
• For instance, for a selected bus cycle time of 0.8 ms, the SL master
can transfer
– one double word each to a max. of 124 slaves/transceiver, or
– 4 double words each to a max. of 31 slaves/transceiver
The remaining times are intervals where a telegram is not sent (NOP).
• Master-slave process data transfer:
– up to 200 slaves/transceiver can be addressed with address gaps
– up to 8 double words individually for each slave/transceiver
– own process data for each slave/transceiver
• Dispatcher transceiver process data transfer:
– up to 200 consecutively addressed transceivers
– up to 8 double words
– the same number of used channels for dispatcher and transceiver
(nodes with a max. number of double words defines the number of
channels for all)
• Data transfer rate: 11 Mbit/s
• Bus topology: Fiber-optic cable ring, each node as
signal amplifier
• Max. distance between two nodes:
− 40 m for plastic fiber-optic cables, or
− 300 m for glass fiber-optic cables.

Table of Contents

Other manuals for Siemens SIMADYN D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMADYN D and is the answer not in the manual?

Siemens SIMADYN D Specifications

General IconGeneral
BrandSiemens
ModelSIMADYN D
CategoryControl Systems
LanguageEnglish

Related product manuals