Closed-loop thyristor current control
5-40 System- and communication configuring D7-SYS - SIMADYN D
Edition 06.2002
When selecting the mode “Pre-control and continuous tracking”
CPI.SVC=1, the current controller converts this actual value into a pre-
control angle CPI.YWP = “EMF angle” and this is added to controller
output CPI.Y.
The pre-control angle CPI.YWP is limited to the effective limits CPI.ZSU
and ZSL.
()
()
-1SV if -1
1 SV if 1
1 SV1- SVarcsin
2
SV
fYWP
<=
+>
+=
==
The actual value of the EMF sensing FB EMF must be calibrated as
precisely as possible. The EMF has a deadtime.
The continuous tracking is only possible with separate sensing due to the
average value generation of the current sensing in the Sitor.
Input CPI.CLU allows the current-dependent limiting of the inverter
control limit to be additionally influenced.
The function of the dynamic inverter stability limit is programmed in FB
CAV and requires the connection (CAV.YAU CPI.CLU)
The lower value of CPI.ALU and CPI.CLU acts as limiting for the inverter
control limit and is the dynamic effective control limit, output at CPI.ZSU.
Tracking
Dynamic
inverter control
limit

Table of Contents

Other manuals for Siemens SIMADYN D

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMADYN D and is the answer not in the manual?

Siemens SIMADYN D Specifications

General IconGeneral
BrandSiemens
ModelSIMADYN D
CategoryControl Systems
LanguageEnglish

Related product manuals