EasyManua.ls Logo

Siemens SIMATIC MOBY D - Page 76

Siemens SIMATIC MOBY D
350 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Planning the MOBY D system
4.5 EMC Guidelines
MOBY D
76 System Manual, 01/2010, J31069-D0147-A6-7618
Prevention of interference by optimum configuration
Good interference suppression can be achieved by installing SIMATIC PLCs on conducting
mounting plates (unpainted). When setting up the control cabinet, interference can be
prevented easily by observing certain guidelines. Power components (transformers, drive
units, load power supply units) should be arranged separately from the control components
(relay control unit, SIMATIC S7).
As a rule:
The effect of the interference decreases as the distance between the interference source
and interference sink increases.
The interference can be further decreased by installing grounded shielding plates.
The load connections and power cables should be installed separately from the signal
cables with a minimum clearance of 10 cm.
3RZHUVXSSO\
&&(8
'ULYH
6KLHOG
SODWH
Figure 4-25 Prevention of interference by optimum configuration

Table of Contents

Related product manuals