Planning the MOBY D system 
  4.5 EMC Guidelines 
MOBY D 
System Manual, 01/2010, J31069-D0147-A6-7618 
79 
4.5.7  Equipotential bonding 
Potential differences between different parts of a plant can arise due to the different design 
of the plant components and different voltage levels. If the plant components are connected 
across signal cables, transient currents flow across the signal cables. These transient 
currents can corrupt the signals. 
Proper equipotential bonding is thus essential.  
●  The equipotential bonding conductor must have a sufficiently large cross section (at least 
10 mm
2
). 
●  The distance between the signal cable and the associated equipotential bonding 
conductor must be as small as possible (antenna effect). 
●  A fine-strand conductor must be used (better high-frequency conductivity). 
●  When connecting the equipotential bonding conductors to the centralized equipotential 
bonding strip (EBS), the power components and non-power components must be 
combined. 
●  The equipotential bonding conductors of the separate modules must lead directly to the 
equipotential bonding strip. 
&DELQHW &DELQHW
,QFRUUHFW
3RZHUVXSSO\
'ULYH
'HYLFH
3/&
(%6
'HYLFH
'HYLFH
,QFRUUHFW
 
Figure 4-28  Equipotential bonding (EBS = Equipotential bonding strip) 
The better the equipotential bonding in a plant, the smaller the chance of interference due to 
fluctuations in potential. 
Equipotential bonding should not be confused with protective earthing of a plant. Protective 
earthing prevents the occurrence of excessive shock voltages in the event of equipment 
faults whereas equipotential bonding prevents the occurrence of differences in potential.