Technical specifications
● With inductive load according to IEC 947-5-1, DC 13
Max. 0.5 Hz
● With lamp load
Max. 10 Hz
Internal limiting of the inductive trip voltage to Typ. L+ (-53 V)
Short-circuit protection of the output Yes, electronic
● Response threshold
Typ. 1 A
Connection of the actuators Using a 40-pin front connector
10.3.2 Digital output module DO 16 x DC 24 V/0.5 A
Article numbers
Standard module: 6ES7 650-8EK70-0AA0
Module with conformal coating: 6ES7 650-8EK70-1AA0
Properties
The DO 16 x DC 24 V/0.5 A is characterized by the following properties:
● 16 outputs, isolated in groups of 4 channels
● Output current 0.5 A
● Rated load voltage 24 V DC
● Suitable for solenoid valves, DC contactors and signal lamps
● Wire break detection at "0" and "1" signal
● Group error display (SF LED)
● Configurable diagnostics
● Configurable diagnostic interrupt
● Configuration in Run (CiR) supported
ET 200PA SMART I/O modules
10.3 Digital output modules
ET 200PA SMART
142 Operating Instructions, 06/2019, A5E34192013-AB