Test and service functions
15.1 Test functions
S7-1500R/H redundant system
474 System Manual, 01/2024, A5E41814787-AF
Testing with watch tables
The following functions are available in the watch table:
Monitoring of tags
Using watch tables, you can monitor the actual values of the individual tags of a CPU user
program.
On the PG/PC
On the display of the CPU
Please note the following requirement for displaying the tag values on the CPU display:
You must specify a symbolic name for each tag in the "Name" column of the force table.
You monitor the following operand areas:
Inputs and outputs (process image) and bit memory
Contents of data blocks
Peripheral inputs and peripheral outputs
Timers and counters
Modifying tags
You use this function to assign values to the individual tags of a user program or a CPU on
the PG/PC. Modifying is also possible with Test with program status.
The following operand areas are modifiable:
Inputs and outputs (process image) and bit memory
Contents of data blocks
Peripheral inputs and peripheral outputs (for example, %I0.0:P, %Q0.0:P)
Timers and counters

Table of Contents

Other manuals for Siemens SIMATIC S7-1500T

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-1500T and is the answer not in the manual?

Siemens SIMATIC S7-1500T Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC S7-1500T
CategoryController
LanguageEnglish

Related product manuals