Number of outputs 16
Cable length
unshielded
600 m
shielded
1000 m
Voltage, current and potential
Rated load voltage L1
Permissible frequency range
79 to 264 V AC
47 to 63 Hz
Total current of outputs (per group)
With fan module
Up to 40°C
max. 4 A 6 A
Up to 60°C
max. 2 A 5 A
Electrical isolation
Between channels and backplane bus
Yes
Between channels
in groups of
Yes
4
Permissible potential difference
Between outputs of different groups
500 V AC (basic insulation)
Test voltage:
1350 Vac (routine test)
Between Mintern and the outputs
250 V AC (reinforced insulation)
Test voltage:
4000 Vac (type test)
1350 AC (routine test)
Current consumption
From backplane bus (5 V)
Maximum 400 mA
From load voltage L + (no load)
1.5 mA
Module power loss Typ. 16 W
Status, interrupts, diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic functions Not configurable
Group fault display
for internal fault
for external fault
Red LED (INTF) fuse failure
Red LED (EXTF) no load voltage
Data for selecting an actuator
Output voltage
For "1" signal
At maximum current at least L1
(-1.3 Vrms)
At minimum current at least L1
(-18.1 Vrms)
Output current
For "1" signal
Rated value
Permitted range
Permitted surge current (per group)
2 A
10 mA to 2 A
Maximum 50 A per cycle
Digital modules
4.19 Digital output module SM 422; DO 16 x AC 120/230 V/2 A (6ES7422-1FF00-0AA0)
S7-400 Automation System Module Data