EasyManua.ls Logo

Siemens Simatic S7-400

Siemens Simatic S7-400
472 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Points to note about checking for "Underflow" with some measuring methods and measuring ranges
There is now underflow in life-zero areas. A value that is too low or is negative is interpreted
as a wire break. You can therefore not configure the underflow check for the SM 431; AI 16 x
16 Bit for the following measuring methods and ranges:
Table 5-67 Points to note when checking for "Underflow"
Measuring method Measuring range
Voltage 1 to 5 V
Current (4-wire sensor) 4 to 20 mA
Current (2-wire sensor) 4 to 20 mA
Points to note about the "Short-circuit to M" diagnostics
You can only configure the check for "Short-circuit to M" for the SM 431; AI 16 x 16 Bit for the
"Current (2-wire transducer)" measuring method.
5.24 Analog input module SM 431; AI 8 x RTD x 16 Bit
(6ES7431-7KF10-0AB0)
5.24.1 Features
Overview
The analog input module SM 431; AI 8 x RTD x 16 bit has the following features:
8 differential inputs for resistance thermometer
Resistance thermometer configurable
Linearization of characteristic curves of the resistance thermometer
Resolution 16 bits
Update rate 25 ms for 8 channels
Configurable diagnostics
Configurable diagnostic interrupt
Configurable limit alarm
Analog section isolated from CPU
The maximum permitted common mode voltage between channels and central grounding
point is 120 V AC
Analog modules
5.24 Analog input module SM 431; AI 8 x RTD x 16 Bit (6ES7431-7KF10-0AB0)
S7-400 Automation System Module Data
292 Reference Manual, Ausgabe 11/2016, A5E00850736-08

Table of Contents

Other manuals for Siemens Simatic S7-400

Related product manuals