Switching frequency
With resistive load
Maximum 100 Hz
With an inductive load in accordance with IEC
947-5-1, DC 13
Maximum 2 Hz at 0.3 A
Maximum 0.5 Hz at 0.5 A
With lamp load
Maximum 10 Hz
(Internal) limitation of inductive switch-off voltage to Typ. - 27 V
Short-circuit protection for output Clocked electronically
Response threshold
Typ. 0.7 to 1.5 A
1
A supply group always consists of 8 neighboring channels, starting from channel 0. Channels 0 to 7,
8 to 15, 16 to 23 and 24 to 32 therefore each form a supply group.
4.17 Digital output module SM 422; DO 32 x DC 24 V/0.5 A
(6ES7422-7BL00-0AB0)
4.17.1 Features
Overview
SM 422; DO 32 x DC 24 V/0.5 A has the following features:
32 outputs, fused and isolated in groups of 8
Output current 0.5 A
Rated load voltage 24 V DC
Group fault display for internal faults (INTF) and external faults (EXTF)
Configurable diagnostics
Configurable diagnostic interrupt
Configurable substitute value output
The status LEDs indicate the system state even if the front connector is not connected.