Loading...
Voltage Current Number of op‐
erating cycles
(typ.)
30 V DC
60 V DC
125 V DC
230 V AC
5.0 A
1.2 A
0.2 A
5.0 A
0.18 million
0.1 million
0.1 million
0.18 million
For an inductive load in accordance with IEC 947-5-1DC 13 / AC 15
Voltage Current Number of op‐
erating cycles
(typ.)
30 V DC
(τ=7 ms max.)
5.0 A 0.1 million
230 V AC
(pf=0.4)
5.0 A 0.1 million
Size of motor starter Maximum 5 pursuant to NEMA
Lamp load Maximum 60 W
Contact wiring (internal) None
Connection of 2 outputs in parallel
For redundant load control
Possible (only outputs with same load volt‐
age)
For increasing the power
Not possible
Control of a digital input Possible
Switching frequency
Mechanical
Maximum 20 Hz
With resistive load
Maximum 10 Hz
With inductive load in accordance with IEC 947-5-1,
DC 13/AC 15
Maximum 1 Hz
With lamp load
Maximum 1 Hz
Note
Use a suppressor circuit in environments with high humidity and where sparks might occur at
the relay contacts. This will increase the service life of the relay contacts.
To install the suppressor circuit, connect an RC element or a varistor in parallel with the relay
contacts or load. The dimensions depend on the size of the load.
Digital modules
4.21 Relay output module SM 422; DO 16 x UC 30/230 V/Rel. 5 A (6ES7422-1HH00-0AA0)
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08 161