Table 5-8 Life-zero input ranges
Units Meas‐
ured val‐
ue in %
Data word Range
2
15
2
14
2
13
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
32511 117,589 0 1 1 1 1 1 1 0 1 1 1 1 1 1 1 1 Overshoot range
27649 ≧100,004 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 1
27648 100,000 0 1 1 0 1 1 0 0 0 0 0 0 0 0 0 0 Nominal range
1 0,003617 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1
0 0,000 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
- 1 -
0,003617
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Undershoot range
- 4864 - 17,593 1 1 1 0 1 1 0 1 0 0 0 0 0 0 0 0
In the event of a wire break, the module reports 7FFF
H
Analog modules
5.4 Representation of analog values
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08 171