The battery/power supply that powers the non-incendive connection must comply with the
following ratings:
Battery/power supply CPU input "Ext. Batt." with cable
Voc Vmax (15 V)
Isc Imax (50 mA)
Ca Ci + Cc (25 nF + Cc)
La Li + Lc (2 mH + Lc)
Cc = Cable capacity
Lc = Cable inductance
Note
The concept of non-incendive field wiring allows the interconnection of devices with non-
incendive field wiring using any wiring method approved for unclassified sites.
If you do not know the capacity and inductance of the cable, you can use the following values:
Cc = 197 pF/m (60 pF/ft.), Lc = 0.66 mH/m (0.2 mH/ft)
Marine Approvals
Classification societies:
ABS (American Bureau of Shipping)
BV (Bureau Veritas)
DNV (Det Norske Veritas)
GL (Germanischer Lloyd)
LRS (Lloyds Register of Shipping)
Class NK (Nippon Kaiji Kyokai)
Safety requirements for installation
The S7-400 automation system is "open-type equipment" in accordance with standard
IEC 61131-2 and therefore EU Directive 2014/35/EU (Low Voltage Directive), and "open type"
in accordance with UL/CSA certification.
To fulfill requirements for safe operation with regard to mechanical stability, flame retardation,
stability, and shock-hazard protection, the following alternative types of installation are
specified:
Installation in a suitable cabinet
Installation in a suitable housing
Installation in a suitably equipped, enclosed operating area.
General specifications
1.1 Standards, certificates and approvals
S7-400 Automation System Module Data
Reference Manual, Ausgabe 11/2016, A5E00850736-08 19