Group fault display
For internal fault
For external fault
Diagnostic information can be read out
Red LED (INTF)
Red LED (EXTF)
Possible
Data for selecting a sensor
Input range (rated values) / input resistance
Resistance thermometer
Pt 100/> 10M
Pt 200/> 10M
Pt 500/> 10M
Pt 1000/> 10M
Ni 100/> 10M
Ni 1000/> 10M
Maximum input voltage for voltage input
(destruction limit)
35 V continuous;
75 V for max. 1 s
(duty factor 1:20)
Connection of encoder
For resistance measurement with 3-wire connection
Possible
(max. permissible line resistance 10 Ohm)
With 4-wire connection
Possible
Characteristic curve linearization Configurable
For RTD resistance temperature detection Pt100...1000,
0.00385 Alpha to
DIN IEC 751
Ni 100...1000,
0.00618 Alpha to
DIN 43760
1
Measuring range
PT100, PT200
-200 °C to +850 °C
PT 500
-200 °C to +800 °C
PT 1000
-200 °C to +240 °C
Ni 100
-60 °C to +250 °C
Ni 1000
-60 °C to +130 °C
User data in engineering format Degrees C/
Degrees F
1
7KF10 does not support all measuring ranges for S7.
Analog modules
5.24 Analog input module SM 431; AI 8 x RTD x 16 Bit (6ES7431-7KF10-0AB0)
S7-400 Automation System Module Data
298 Reference Manual, Ausgabe 11/2016, A5E00850736-08