PS 407 10A and PS 407 10A R technical specifications
Dimensions, weight and cable cross-sections
Dimensions W x H x D (mm)
Weight
Cable cross-section
50x290x217
1.2 kg
3x1.5 mm
2
(stranded wire with wire end ferrule with
insulating sleeve; use hose line only)
Input variables
Input voltage
Rated value
120/230 V DC
120/230 V AC
Permitted range
88 to 300 V DC
85 to 264 V AC
(wide range input)
Line frequency
Rated value
50/60 Hz
Permitted range
47 to 63 Hz
Rated input current
With 120 V AC
0.9 A
With 120 V DC
1.0 A
At 230 V AC
0.5 A
At 230 V DC
0.5 A
Inrush current
At 230 V AC
Peak value 63 A, full width at half maximum 1 ms*
At 300 V DC
Peak value 58 A, full width at half maximum 1 ms*
Leakage current < 3.5 mA
Output variables
Output voltage
Rated values
5.1 V DC/24 V DC
Output current
Rated values
5 V DC: 10 A
24 V DC: 1.0 A
Parameters
Protection class pursuant to IEC 60536 I, with protective conductor
Overvoltage category II
Pollution degree 2
Rated voltage U
e
0 < U
e
≤ 50 V
150 V < U
e
≤ 300 V
Test voltage
700 V DC (secondary <-> PE)
2200 V DC (primary <-> secondary/PE)
Backup for power failures > 20 ms
at a repeat rate of 1 s, meets NAMUR recommen‐
dation NE 21
Power consumption 95 W
Power loss 20 W
Backup current maximum of 100 µA when power off
Power supply modules
3.9 Power supply modules PS 407 10A (6ES7407-0KA02-0AA0) and PS 10A R (6ES7407-0KR02-0AA0)