Ambient air temperature
°C
Derating factor according to EN 60204-1, Table D1
50 0.82
55 0.71
60 0.58
Assignment, terminal boxes and max. cross-sections
Table 9-4 Terminal box data
Terminal
box type
Shaft
height
Cable entry
(power)
Cable entry
(external sig‐
nals)
Outer cable di‐
ameter, max.
mm
2)
Number of main ter‐
minals
Max. cross-
section
per
terminal
mm
2
Max.
current
per
terminal
A
3)
gk803 SH80 1 x M25 x 1.5 1 x M16 x 1.5
1)
20 Phases: 3 x M5
Grounding: 2 x M5
1 x 10 52
gk806 SH80 1 x M25 x 1.5 1 x M16 x 1.5
1)
20 Phases: 6 x M5
Grounding: 2 x M5
1 x 10 52
gk813 SH100 1 x M32 x 1.5 1 x M16 x 1.5
1)
24.2 Phases: 3 x M5
Grounding: 2 x M5
1 x 16 70
gk823 SH100 1 x M32 x 1.5 1 x M16 x 1.5
1)
24.2 Phases: 3 x M5
Grounding: 2 x M5
1 x 16 70
gk826 SH100 1 x M32 x 1.5 1 x M16 x 1.5
1)
24.2 Phases: 6 x M5
Grounding: 2 x M5
1 x 10 52
gk833 SH132 1 x M40 x 1.5 1 x M16 x 1.5
1)
32 Phases: 3 x M6
Grounding: 2 x M6
1 x 35 110
gk843 SH132 1 x M50 x 1.5 1 x M16 x 1.5
1)
38 Phases: 3 x M6
Grounding: 2 x M6
1 x 50 133
gk846 SH132 1 x M50 x 1.5 1 x M16 x 1.5
1)
38 Phases: 6 x M6
Grounding: 2 x M6
1 x 25 88
gk863 SH160 1 x M50 x 1.5 1 x M16 x 1.5
1)
38 Phases: 3 x M6
Grounding: 2 x M6
1 x 50 133
gk873 SH160 1 x M63 x 1.5 1 x M16 x 1.5
1)
42.6 Phases: 3 x M6
Grounding: 2 x M6
1 x 50 133
gk874 SH160 1 x M63 x 1.5 1 x M16 x 1.5
1)
42.6 Phases: 3 x M10
Grounding: 2 x M6
2 x 70 240
1XB7322-
P05
SH180
to
SH280
2 x M50 x 1.5 1 x M16 x 1.5
4)
38 Phases: 3 x M12
Grounding: 4 X M6e
2 x 50 210
1XB7422-
P06
SH180
to
SH280
2 x M63 x 1.5 1 x M16 x 1.5
4)
53 Phases: 3 x M12
Grounding: 4 x M8
2 x 70 270
Electrical connection
9.3System integration
1PH8 SIMOTICS M main motors
Con󹪝guration Manual, 12/2022, A5E51895839A 231

Table of Contents