Diagnostics
5.2 Diagnostics using LEDs
Commissioning with Startdrive
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
139
Control Unit 320-2 when the powering up
Table 5- 2 Load software
LED
State
Comment
RDY
COM
OPT
Red Orange Orange Reset Hardware reset
RDY LED lights up red, all other LEDs light up or-
ange
Red
Red
Off
BIOS loaded
Red
Flashing light
2 Hz
Red Off BIOS error
Error occurred while loading the BIOS
Red
Flashing light
2 Hz
Red
Flashing light
2 Hz
Off File error
Memory card not inserted or faulty
Software on memory card not present or corrupt-
ed
Table 5- 3 Firmware
LED
State
Comment
RDY
COM
OPT
Orange
Off
Off
Initializing
Red Orange
Flashing light
Off Firmware loading RDY LED lights up red, COM LED flashes orange
without fixed flash frequency
Red
Off
Off
Firmware loaded
Red
flashing light
0.5 Hz
Red
flashing light
0.5 Hz
Off Firmware loaded Firmware-Firmware/Project download completed.
Waiting for POWER ON.
Off Red Off Firmware
checked
(no CRC error)
Red
flashing light
0.5 Hz
Red
flashing light
0.5 Hz
Off Firmware
checked
(CRC error)
CRC invalid
Alternating Running See the table below