Diagnostics
5.2 Diagnostics using LEDs
Commissioning with Startdrive
140 Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0
Control Unit 320-2 in operation
Table 5- 4 CU320-2 PN Control Unit description of the LEDs after powering up
LED
Color
State
Description, cause
Remedy
RDY
(READY)
OFF Electronic power supply is missing or outside
permissible tolerance range.
Check the power supply.
Green Continuous light The component is ready for operation and cyclic
DRIVE-CLiQ communication is taking place.
Flashing light
0.5 Hz
Commissioning/reset
Flashing light
2 Hz
Writing to the memory card
Red Flashing light
2 Hz
General errors Check parameterization /
configuration data
Red/
green
Flashing light
0.5 Hz
Control Unit is ready for operation.
However, there are no software licenses.
Obtain licenses.
Orange Flashing light
0.5 Hz
Updating the firmware of the DRIVE-CLiQ com-
ponents
Flashing light
2 Hz
DRIVE-CLiQ component firmware update com-
plete. Wait for POWER ON for the components
in question.
Turn POWER ON for the
components in question
Green/
orange
or
red/
orange
Flashing light
2 Hz
Component detection via LED is activated
(p0124[0]).
Note
:
Both options depend on the LED status when
component recognition is activated via
p0124[0] = 1.
Green/
orange
or
red/
orange
Flashing light
1 Hz
CU detection via DCP flashing.
Note
:
Both options depend on the LED status when
component recognition is activated via DCP.
Green Flashing light:
Switch-on/off
ratio:
500 ms on
3000 ms off
PROFIenergy energy saving mode is active.