Order no.:
6SL3217-0CE
Frame Size A Frame Size B Frame Size C Frame Size D
Overvoltage category Mains input terminals (L1, L2, L3): III 
Digital output terminals (DO1) 
3)
: II, max. 250 V
In accordance with IEC 61800-5-1
Pollution class II, in accordance with IEC 61800-5-1
Noise level < 80dB for the whole product family
Control method Linear V/f control; Quadratic V/f control; V/f control with Flux Current Control (FCC)
Fixed frequency 3, programmable
Skip frequency: 1
Setpoint resolution 0.01 Hz digital input
Digital inputs 3, programmable (isolated)
Analog input 1, programmable (0 to 10 V or 0 to 20 mA)
Relay output 1, programmable, 250 V AC / max. 2 A (inductive), 30 V DC / max. 5 A (resistive)
Analog output 1, programmable (0 to 10 V or 0 to 20 mA, max. 500 ohm in current mode / min. 5000 ohm 
in voltage mode)
Braking  DC braking, compound braking
Protection functions ① Short circuit protection ② Over-current protection ③ Over-/Under-voltage protection 
④ Inverter and motor over-temperature protections ⑤ Ground fault protection ⑥ Stall 
prevention ⑦ Motor blocking protection ⑧ Parameter interlock
Max.
Motor 
cable 
length
Without 
choke
Unshielded 50 m 50 m 100 m 100 m
Shielded 30 m 30 m 50 m 50 m
With 
choke
Unshielded 100 m 100 m 200 m 250 m
Shielded 60 m 60 m 100 m 150 m
Mechanical data
Outline 
dimen-
sions (mm)
H 230 260 331 401
W 140 150 218 260
D 
4)
155 (138 ) 159 (142) 203 (186) 223 (210)
Note: The outline dimensions of the operator panel are 91 x 97 x 30 (H x W x D, in mm).
Weight (kg) 
5)
2.2 2.9 8.1 10.1
Mounting method For inverter with assembled operator panel:
● Wall mounting without optional mounting kit
● Push-through mounting with optional mounting kit
For removable operator panel:
● Mounted to cabinet door
Cooling method Natural cooling  Forced cooling  Forced cooling Forced cooling
Environmental conditions
Technical data
SINAMICS V10
116 Operating Instructions, 08/2011, A5E03453178 (this is not an order number)