Par.
No.
Name Range Unit Default value
P1133 Ramp-down final
rounding time
0.00 - 40.00 s 0.00 0.00 0.00 0.00 0.00 0.00
P1080 Min. frequency 0.00 - 300.00 Hz 0.00 20.00 0.00 0.00 5.00 0.00
P1082 Max. frequency 0.00 - 300.00 Hz 50.00 50.00 50.00 50.00 50.00 50.00
P1300 Control mode 0 - 2 -- 0 2 0 0 0 0
P1310 Continuous boost 0.0 - 250.0 % 50.0 0.0 50.0 0.0 50.0 50.0
P1311 Acceleration boost 0.0 - 250.0 % 0.0 0.0 0.0 50.0 0.0 0.0
P1312 Starting boost 0.0 - 250.0 % 0.0 0.0 0.0 0.0 0.0 0.0
P1240 Configuration of Vdc
controller
0 - 1 -- 1 1 1 1 1 1
P1243 Dynamic factor of Vdc-
max
10 - 200 % 100 100 100 100 100 100
P1230 Enable DC braking 0:0 - 4,000:0 -- 0:0 0:0 0:0 0:0 0:0 0:0
P1232 DC braking current 0 - 250 % 0 0 0 0 0 0
P1233 Duration of DC braking 0 - 250 s 0 0 0 0 0 0
P1200 Flying start 0 - 6 -- 0 1 0 0 0 0
P1202 Motor-current: Flying start 10 - 200 % 100 100 100 100 100 100
P1203 Search rate: Flying start 10 - 200 % 100 100 100 100 100 100
P1210 Automatic restart 0 - 6 -- 1 2 1 1 1 1
P0640 Motor overload factor [%] 10.0 - 400.0 % 150.0 150.0 150.0 150.0 150.0 150.0
P1110 Inhibit negative setpoint 0.0 - 2036.F -- 0 1 1 0 0 0
Commissioning
6.2 Application macros
SINAMICS V10
Operating Instructions, 08/2011, A5E03453178 (this is not an order number) 57